| Voltage | Dual 120/277 Optional multi-tap 208/220/240 voltage available. |
| Charge Rate / Power | “ON” LED indicator light and push-to-test switch for mandated code compliance. |
| Battery | 6v maintenance free, rechargeable NiCd battery. |
| Transfer Switch | Internal solid state. Automatically connects the internal battery to LED board and lamp heads for minimum 90min. emergency illumination. |
| Charger | Fully automatic, solid state, two rate charger initiates battery charging to recharge a discharged battery in 24 hrs. |
| Mounting | Surface mount via easy connect backplate, which fits most standard J boxes and snaps into place making internal electrical connections. Top and side knock-outs available for conduit application. Suitable for wall mount. |
| Construction | Injection molded, engineering grade, 5VA flame retardant, high impact resistant thermoplastic. |
| Option SDT | Self diagnosis feature performs monthly, biannual, and annual tests to ensure reliable operation and meet electrical and life safety codes. |
| Option HL | 12-LED heads provide increased center-to-center spacing (1.5w per head). |
| Option SPV | Tested 120/347v to meet requirements of CSA C22.2 No. 141.10 standard for emergency lighting equipment. |
| Option CEC | Certified to CEC under Title 20 Regulations. |
| Option CSA | Units tested to meet requirements of CAN/USA-c22.2 No. 141- 02 standard for unit equipment. |